Influence of the supply of reactive power in the calculation of the transfer capability

Nenhuma Miniatura disponível

Data

2004-12-01

Autores

Gaino, Fábio Cassucci [UNESP]
Padilha-Feltrin, Antonio [UNESP]

Título da Revista

ISSN da Revista

Título de Volume

Editor

Resumo

This paper presents some initial concepts for including reactive power in linear methods for computing Available Transfer Capability (ATC). It is proposed an approximation for the reactive power flows computation that uses the exact circle equations for the transmission line complex flow, and then it is determined the ATC using active power distribution factors. The transfer capability can be increased using the sensitivities of flow that show the best group of buses which can have their reactive power injection modified in order to remove the overload in the transmission lines. The results of the ATC computation and of the use of the sensitivities of flow are presented using the Cigré 32-bus system. © 2004 IEEE.

Descrição

Palavras-chave

Distribution Factor, Linear ATC, Maximum Capability Transfer, Reactive Power Flow, Reactive Support, Sensitivities of flow, Distribution factor, Linear available transfer capability (ATC), Maximum capability transfer, Reactive power flow, Reactive support, Algorithms, Computational methods, Data reduction, Electric lines, Electric power transmission, Sensitivity analysis, Electric power distribution

Como citar

2004 IEEE/PES Transmission and Distribution Conference and Exposition: Latin America, p. 190-195.