Development of SNO2 based varistors -electrical behavior and pulse degradation comparatively to ZNO varistors
Nenhuma Miniatura disponível
Data
2017-02-07
Autores
Bassi, W.
Ramirez, M. A. [UNESP]
Bueno, P. R. [UNESP]
Longo, E. [UNESP]
Varela, J. A. [UNESP]
Título da Revista
ISSN da Revista
Título de Volume
Editor
Resumo
This work presents the most relevant aspects of the SNO2 based varistors technology and a comparative study of its non linear behavior in relation to ZnO (modified Matsuoka system) varistors. Electrical performance at low and high impulse currents is presented. The SNO2 system had shown better performance in important parameters when compared to SNO2 system such as higher non linear coefficients in the entire range of measured currents and much higher electrical breakdown field. It was also evaluated the degradation both technologies of varistors subjected to lightning current pulses (8/20 μs) resulting a more severe degradation in the ZnO varistors. The improved behavior of the SNO2 system forms the basis to a forthcoming design of surge arresters and surge protective devices based on such technology.
Descrição
Palavras-chave
degradation, energy, protection, SNO2, surge arresters, technology, varistors, ZnO
Como citar
2010 30th International Conference on Lightning Protection, ICLP 2010.