Overvoltage analysis of transmission towers considering the influence of tower-footing impedance

Nenhuma Miniatura disponível

Data

2017-11-21

Autores

De Araújo, Anderson Ricardo Justo [UNESP]
De Seixas, Claudiner Mendes [UNESP]
Kurokawa, Sérgio [UNESP]
Kordi, Behzad

Título da Revista

ISSN da Revista

Título de Volume

Editor

Resumo

Lightning is one of the main causes of outages due to backflashover mechanism in power systems. In this context, the tower-footing impedance presents a key role in the overvoltages caused by this phenomenon. Tower-footing impedance is traditionally modelled as a pure resistance, which is a good approximation, at low frequencies. However, the inductance and resistance of the tower-footing impedance strongly depend on the frequency at higher frequencies of the spectrum that is covered by lightning strokes. As such, their frequency dependence must be considered for accurate calculation of transient responses. Using the Vector Fitting technique, the admittance of grounding electrode buried in soil is represented by a lumped parameter circuit. The circuit model can be connected to transient transmission line models which enables the calculation of the voltages at the cross-arms of the tower. This paper shows the influence of tower-footing impedance of vertical electrodes on the overvoltage caused by a lightning striking at the tower top. The analysis will show how the soil characteristics and geometrical parameters affect the overvoltages at a typical transmission tower.

Descrição

Palavras-chave

backjlashovers, tower-footing impedance, transmission tower

Como citar

2017 International Symposium on Lightning Protection, XIV SIPDA 2017, p. 287-294.