Baldan, Carlos Alberto [UNESP]Lamas, Jerika SuelyShigue, Carlos YujiroRuppert Filho, Ernesto2014-05-202014-05-202009-06-01IEEE Transactions on Applied Superconductivity. Piscataway: IEEE-Inst Electrical Electronics Engineers Inc, v. 19, n. 3, p. 1810-1813, 2009.1051-8223http://hdl.handle.net/11449/9013A fault current limiter (FCL) based on an arrangement of parallel connected high temperature superconducting tapes constituting a limiter element was designed and tested in 220 V line for a fault current peak between 1 kA to 2 kA. The limiter employed second generation (2G) HTS tapes of YBCO coated conductor reinforced with stainless steel. Four tapes were electrically connected in parallel with 0.4 m effective length per element wherein 16 elements connected in series constitutes a single-phase unit. The FCL performance was evaluated through over-current and current fault tests. Its recovery characteristics were used to design the shunt protection. The designed limiting ratio is 4 for 16 elements and the experimental result for one element showed a 20% limiting ratio. For the fault current test one element can withstand five cycles of fault without degradation. It was observed recovery times below 0.5 s under nominal load using a shunt resistance of 173 m Omega.1810-1813engCurrent limiting ratiosuperconducting fault current limiterYBCO coated conductorYBCO recovery characteristicsFault Current Limiter Using YBCO Coated Conductor-The Limiting Factor and Its Recovery TimeArtigo10.1109/TASC.2009.2019043WOS:000268282100169Acesso restrito1689995854269032