Fernandes Pereira, Rodrigo Aparecido [UNESP]Wesz da Silva, Luis GustavoKezunovic, MladenSanches Mantovani, Jose Roberto [UNESP]2014-05-202014-05-202009-04-01IEEE Transactions on Power Delivery. Piscataway: IEEE-Inst Electrical Electronics Engineers Inc, v. 24, n. 2, p. 852-862, 2009.0885-8977http://hdl.handle.net/11449/9857A fault location algorithm for distribution feeders based on matching during-fault voltage sags is presented. The basic principle of the algorithm is based on the fact that when a fault occurs on the feeder, voltage sags propagate presenting different characteristics for each feeder node. Knowing the voltage sag characteristics, it is possible to locate the faulty node or the faulty area of the feeder. This voltage-based approach ensures the efficiency and robustness of the algorithm, which provides suitable and accurate results. An overhead, three-phase, three-wire, 13.8 kV, 134-node, real-life feeder model is used to evaluate the algorithm. Test results show that the algorithm is quite suitable due to not only the faulted point being located, but also a faulted area being identified providing important information to direct the maintenance crew seeking to repair any fault inflicted damage.852-862engFault locationpower distributionvoltage measurementvoltage sagsImproved Fault Location on Distribution Feeders Based on Matching During-Fault Voltage SagsArtigo10.1109/TPWRD.2009.2014480WOS:000265093000044Acesso restrito0614021283361265