Harmonic Resonance in Electrical Grids with Photovoltaic Distributed Generation

Nenhuma Miniatura disponível

Data

2016-01-01

Autores

Fortes, Rarison R. A.
Oliveira, Luis C. O. [UNESP]
Souza, Julio B. de [UNESP]
Buzo, Ricardo F. [UNESP]
Perez Alvarez, Juan J. [UNESP]
IEEE

Título da Revista

ISSN da Revista

Título de Volume

Editor

Ieee

Resumo

In this paper it is presented the analysis of an electric power distribution branch containing a photovoltaic system, considering the generation and propagation of harmonic distortion. The obtained results refer to an operational configuration of the grid with a parallel resonance at a harmonic frequency generated by the photovoltaic system due to an installed capacitor bank. Power Simulator-PSIM is used as a simulation platform to evaluate the propagation of current harmonic distortion as well the associated voltage harmonic distortions. A technique to identify the network resonance frequencies is also proposed. Under these conditions, violations of the voltage total harmonic distortion operational limits are evaluated, as well as the recommended operating limits for the installed capacitor bank.

Descrição

Palavras-chave

harmonic distortion, distributed generation, power quality, parallel resonance, photovoltaic system

Como citar

Proceedings Of 2016 17th International Conference On Harmonics And Quality Of Power (ichqp). New York: Ieee, p. 214-219, 2016.