Levenberg-Marquardt application to two-phase nonlinear parameter estimation for finned-tube coil evaporators

Carregando...
Imagem de Miniatura

Data

2006-01-01

Autores

Bueno, S. S.
Dias, J. P.
Seixlack, A. L.
Aparecido, J. B.

Título da Revista

ISSN da Revista

Título de Volume

Editor

Hindawi Publishing Corporation

Resumo

A procedure for calculation of refrigerant mass flow rate is implemented in the distributed numerical model to simulate the flow in finned-tube coil dry-expansion evaporators, usually found in refrigeration and air-conditioning systems. Two-phase refrigerant flow inside the tubes is assumed to be one-dimensional, unsteady, and homogeneous. In themodel the effects of refrigerant pressure drop and the moisture condensation from the air flowing over the external surface of the tubes are considered. The results obtained are the distributions of refrigerant velocity, temperature and void fraction, tube-wall temperature, air temperature, and absolute humidity. The finite volume method is used to discretize the governing equations. Additionally, given the operation conditions and the geometric parameters, the model allows the calculation of the refrigerant mass flow rate. The value of mass flow rate is computed using the process of parameter estimation with the minimization method of Levenberg-Marquardt minimization. In order to validate the developed model, the obtained results using HFC-134a as a refrigerant are compared with available data from the literature.

Descrição

Palavras-chave

Como citar

Mathematical Problems In Engineering. New York: Hindawi Publishing Corporation, 13 p., 2006.