Reducing the spurious oscillations in the lumped parameters model using low-pass filter

dc.contributor.authorDe Araújo, Anderson Ricardo Justo [UNESP]
dc.contributor.authorDa Silva, Rodrigo Cleber [UNESP]
dc.contributor.authorKurokawa, Sergio [UNESP]
dc.contributor.institutionUniversidade Estadual Paulista (Unesp)
dc.date.accessioned2018-12-11T17:25:02Z
dc.date.available2018-12-11T17:25:02Z
dc.date.issued2015-04-01
dc.description.abstractVoltages and currents in the transmission line are described by differential equations that are difficult to solve due soil and skin effect that has to be considered for accurate results, but it increases their complexity. Therefore there are some models to study the voltages and currents along in transmission line. The distributed parameters model that transforms the equations in time domain to the frequency domain and once the solutions are obtained, they are converted to time domain using the Inverse Laplace Transform using numerical methods. Another model is named lumped parameters model and it considers the transmission line represented by a π-circuit cascade and the currents and voltages are described by state equations. In the simulations using the lumped parameters model, it can be observed the presence of spurious oscillations that are independent of the quantity of π-circuits used and do not represent the real value of the transient. In this work will be projected a passive low-pass filter directly inserted in the lumped parameters model to reduce the spurious oscillations in the simulations, making this model more accurate and reliable for studying the electromagnetic transients in power systems.en
dc.description.affiliationUniversidade Estadual Paulista (UNESP)
dc.description.affiliationUnespUniversidade Estadual Paulista (UNESP)
dc.format.extent1029-1034
dc.identifierhttp://dx.doi.org/10.1109/TLA.2015.7106353
dc.identifier.citationIEEE Latin America Transactions, v. 13, n. 4, p. 1029-1034, 2015.
dc.identifier.doi10.1109/TLA.2015.7106353
dc.identifier.file2-s2.0-84929300825.pdf
dc.identifier.issn1548-0992
dc.identifier.scopus2-s2.0-84929300825
dc.identifier.urihttp://hdl.handle.net/11449/177345
dc.language.isopor
dc.relation.ispartofIEEE Latin America Transactions
dc.relation.ispartofsjr0,253
dc.rights.accessRightsAcesso aberto
dc.sourceScopus
dc.subjectdistributed parameters
dc.subjectElectromagnetic transients
dc.subjectlow-pass filter
dc.subjectlumped parameters
dc.subjecttransmission lines
dc.titleReducing the spurious oscillations in the lumped parameters model using low-pass filteren