Logotipo do repositório
 

Publicação:
A geometrical view for multiple gross errors detection, identification, and correction in power system state estimation

Carregando...
Imagem de Miniatura

Orientador

Coorientador

Pós-graduação

Curso de graduação

Título da Revista

ISSN da Revista

Título de Volume

Editor

Tipo

Artigo

Direito de acesso

Resumo

In this paper a geometrical approach is described to detect, identify, and recover multiple gross errors in power system state estimation. Using the classical WLS estimator, the measurement residuals is computed, and then the error is composed. For the detection and identification of the measurements with gross errors, the composed measurement error in the normalized form (CME N) is used. The measurement magnitude corrections otherwise are performed using the composed normalized measurement error (CNE). To give support to the detection and identification of the measurements containing gross errors, a generalization of the classical largest normalized residual test is provided. © 1969-2012 IEEE.

Descrição

Palavras-chave

Composing errors, gross errors analysis, orthogonal projections, recovering errors, state estimation

Idioma

Inglês

Como citar

IEEE Transactions on Power Systems, v. 28, n. 3, p. 2128-2135, 2013.