This paper investigates the influence of frequency-dependent soil parameters with variable water content in the transient responses of single-circuit three-phase transmission line (TL) subjected to lightning subsequent return stroke. For this purpose, we use the Nakagawa's approach to compute the ground-return impedance and admittance matrices the frequency-dependent soil modeled by Messier is employed. With the Nakagawa's approach, four water contents of 0.90%, 2.57%, 4.04% and 11.57% are selected with results in low-frequency resistivity of 5000, 1000, 500 and 100 Ω.m. The transient responses for single-circuit three-phase line located above soils of 100, 500, 1000, and 5000 Ω.m considering the frequency-constant soil using the Carson's approach are compare. Results demonstrated that the inclusion of frequency dependence of soil leads to an expressive reduction of approximately 19.52% and 60.16% in the generated voltage peaks (first and third) for this TL located above a high-resistive soil of 5000 Ω.m and lower water content W = 0.90%. This work shows the impact of the frequency-dependent soil that must be taken into account for adequate transient in power systems.

Description

Keywords

frequency-dependent soils, lightning, transient analysis, transmission lines, water content

Language

English

Citation

2021 Workshop on Communication Networks and Power Systems, WCNPS 2021.

Related itens

Sponsors

Units

Departments

Undergraduate courses

Graduate programs

Other forms of access