Repository logo

Fault Current Limiter Using YBCO Coated Conductor-The Limiting Factor and Its Recovery Time

Loading...
Thumbnail Image

Advisor

Coadvisor

Graduate program

Undergraduate course

Journal Title

Journal ISSN

Volume Title

Publisher

Institute of Electrical and Electronics Engineers (IEEE)

Type

Article

Access right

Acesso restrito

Abstract

A fault current limiter (FCL) based on an arrangement of parallel connected high temperature superconducting tapes constituting a limiter element was designed and tested in 220 V line for a fault current peak between 1 kA to 2 kA. The limiter employed second generation (2G) HTS tapes of YBCO coated conductor reinforced with stainless steel. Four tapes were electrically connected in parallel with 0.4 m effective length per element wherein 16 elements connected in series constitutes a single-phase unit. The FCL performance was evaluated through over-current and current fault tests. Its recovery characteristics were used to design the shunt protection. The designed limiting ratio is 4 for 16 elements and the experimental result for one element showed a 20% limiting ratio. For the fault current test one element can withstand five cycles of fault without degradation. It was observed recovery times below 0.5 s under nominal load using a shunt resistance of 173 m Omega.

Description

Keywords

Current limiting ratio, superconducting fault current limiter, YBCO coated conductor, YBCO recovery characteristics

Language

English

Citation

IEEE Transactions on Applied Superconductivity. Piscataway: IEEE-Inst Electrical Electronics Engineers Inc, v. 19, n. 3, p. 1810-1813, 2009.

Related itens

Units

Undergraduate courses

Graduate programs

Other forms of access