Publicação: Comparative Analysis of the Influence of PV Bus Representation in the Current Injection Continuation Power-Flow
Carregando...
Data
Autores
Orientador
Coorientador
Pós-graduação
Curso de graduação
Título da Revista
ISSN da Revista
Título de Volume
Editor
Ieee-inst Electrical Electronics Engineers Inc
Tipo
Artigo
Direito de acesso
Acesso aberto

Resumo
This paper presents a comparative analysis of different voltage-controlled bus (PV bus) representations and their influence in the convergence of Newton-Raphson continuation power-flow based on current injection formulation written in polar coordinates. The continuation power-flow methods developed with these different representations were applied to trace the P-V curve of IEEE tests systems and of two realistic Brazilian systems of 638 and 787 buses, corresponding to parts of the South-Southeast Brazilian system. The obtained results show an improvement in the performance of the current injection continuation power flow method obtained by a new representation.
Descrição
Palavras-chave
Continuation method, Newton-Raphson power flow, PV bus representation, Maximum loading point, P-V curve
Idioma
Inglês
Como citar
Ieee Latin America Transactions. Piscataway: Ieee-inst Electrical Electronics Engineers Inc, v. 16, n. 12, p. 2910-2916, 2018.