Estimation of parameters for faulted transposed transmission lines
Nenhuma Miniatura disponível
Data
2018-01-01
Autores
Rivera Pineda, Julia Teresa [UNESP]
Kurokawa, Sergio [UNESP]
IEEE
Título da Revista
ISSN da Revista
Título de Volume
Editor
Ieee
Resumo
This paper presents a method to estimate transmission line parameters for transposed lines from faulted current and voltage measurements at the line's terminals, in the time domain. The measurements are transformed to the modal domain, using Clarke's transformation matrix, and related to the modal impedance and admittance using the pi-circuit representation. The lumped modal parameters calculated by the least square method are firstly distributed along the line and finally converted to the phase domain. The method is tested for both short and open circuit faults and proved invariant and precise for transmission lines within 800km of length.
Descrição
Palavras-chave
Clarke's Transformation Matrix, Least Square Method, Transmission Line Parameter Estimation, Transient state, Single pi-circuit