Introduction of a Non-Conventional Solution for Amazon Transmission System: Analysis of the Electric Aspects

Nenhuma Miniatura disponível

Data

2011-01-01

Autores

Pinto, A. J. G.
Costa, E. C. M.
Kurokawa, S. [UNESP]
Pissolato, J.
IEEE

Título da Revista

ISSN da Revista

Título de Volume

Editor

Ieee

Resumo

This article shows an analysis of the longitudinal electric parameters of a three-phase transmission line/section using a 280-meter high steel tower. This characteristic, the height of the line conductors and distance between them, are intrinsic related to the longitudinal and transversal parameters of the line. By this means, an accurate study was carried out in order to show the electric variations between a transmission line using the new technology and a three-phase conventional 440 kV line for a wide range of frequencies and a variable soil resistivity. In addition, by using a digital line model, simulations are carried out in time domain to analyze critical overvoltage transients on the studied line.

Descrição

Palavras-chave

Transmission line, steel towers, line parameters, electromagnetic transients

Como citar