Publicação: Caracterização química e mineralógica da incrustação em rede de ferro fundido e potencial de recuperação da capacidade hidráulica
Carregando...
Data
Orientador
Coorientador
Pós-graduação
Curso de graduação
Título da Revista
ISSN da Revista
Título de Volume
Editor
Assoc Brasileira Engenharia Sanitaria Ambiental
Tipo
Artigo
Direito de acesso
Acesso aberto

Resumo
The purpose of this work was to characterize chemical and mineralogical the water supply networks and to assess the hydraulic recovery on high-degraded pipe. Thus, the resistance (by pitometric essays), chemical analyses (ICP-MS and ICP-ES), mineralogical analysis (petrographic thin sections, X-ray difractometry and scanning electronic microscopy), hardness (Mohs scale) and simulations for pipe's change and rehabilitations scenarios were investigated (from Scenario 1 to 4). The results showed that the high-degraded pipe had a limited recovery (from 3,9 to 14,0 m(0,367).s(-1)). The deposits were formed by oxide and hydroxide of iron (magnetite and goethite), which are materials of high hardness (6 on Mohs scale). The simulations indicated the required power ratio (C-i/C-1) around 86.00, 1.00 and 0.02% in relation to present scenario.
Descrição
Palavras-chave
water supply network, deposits, inlay, head-loss
Idioma
Português
Como citar
Engenharia Sanitaria E Ambiental. Rio de Janeiro: Assoc Brasileira Engenharia Sanitaria Ambiental, v. 17, n. 3, p. 305-314, 2012.