Publicação: Continuation fast decoupled power flow with secant predictor
Carregando...
Data
Orientador
Coorientador
Pós-graduação
Curso de graduação
Título da Revista
ISSN da Revista
Título de Volume
Editor
Institute of Electrical and Electronics Engineers (IEEE)
Tipo
Artigo
Direito de acesso
Acesso restrito
Resumo
The conventional Newton and fast decoupled power flow methods are considered inadequate for obtaining the maximum loading point of power systems due to ill-conditioning problems at and near this critical point. At this point, the Jacobian matrix of the Newton method becomes singular. In addition, it is widely accepted that the P-V and Q-theta decoupling assumptions made for the fast decoupled power flow formulation no longer hold. However, in this paper, it is presented a new fast decoupled power flow that becomes adequate for the computation of the maximum loading point by simply using the reactive power injection of a selected PV bus as a continuation parameter. Besides, fast decoupled methods using V and 0 as parameters and a secant predictor are also presented. These new versions are compared to each other with the purpose of pointing out their features, as well as the influence of reactive power and transformer tap limits. The results obtained for the IEEE systems (14 and 118 buses) show that the characteristics of the conventional method are enhanced and the region of convergence around the singular solution is enlarged.
Descrição
Palavras-chave
continuation power flow, fast decoupled power flow, maximum loading point, voltage collapse
Idioma
Inglês
Como citar
IEEE Transactions on Power Systems. Piscataway: IEEE-Inst Electrical Electronics Engineers Inc., v. 18, n. 3, p. 1078-1085, 2003.