Publicação:
Practical comparisons among electronic energy meters, a precision energy meter and IEEE1459 for reactive energy measurements, under unbalanced and non-sinusoidal conditions

dc.contributor.authorE Melo, G. A. [UNESP]
dc.contributor.authorFazio, A. [UNESP]
dc.contributor.authorSampaio, L. P. [UNESP]
dc.contributor.authorDe Brito, M. A. G. [UNESP]
dc.contributor.authorOliveira, R. A N [UNESP]
dc.contributor.authorCanesin, C. A. [UNESP]
dc.contributor.institutionUniversidade Estadual Paulista (Unesp)
dc.date.accessioned2014-05-27T11:27:17Z
dc.date.available2014-05-27T11:27:17Z
dc.date.issued2012-12-01
dc.description.abstractThis paper presents a practical experimentation for comparing reactive/non-active energy measures, considering three-phase four-wire non-sinusoidal and unbalanced circuits, involving five different commercial electronic meters. The experimentation set provides separately voltage and current generation, each one with any waveform involving up to fifty-first harmonic components, identically compared with acquisitions obtained from utility. The experimental accuracy is guaranteed by a class A power analyzer, according to IEC61000-4-30 standard. Some current and voltage combination profiles are presented and confronted with two different references of reactive/non-active calculation methodologies; instantaneous power theory and IEEE 1459-2010. The first methodology considers the instantaneous power theory, present into the advanced mathematical internal algorithm from WT3000 power analyzer, and the second methodology, accomplish with IEEE 1459-2010 standard, uses waveform voltage and current acquisition from WT3000 as input data for a virtual meter developed on Mathlab/Simulink software. © 2012 IEEE.en
dc.description.affiliationPower Electronics Laboratory - Electrical Engineering Department São Paulo State University - UNESP, Ilha Solteira
dc.description.affiliationUnespPower Electronics Laboratory - Electrical Engineering Department São Paulo State University - UNESP, Ilha Solteira
dc.identifierhttp://dx.doi.org/10.1109/INDUSCON.2012.6451400
dc.identifier.citation2012 10th IEEE/ias International Conference on Industry Applications (induscon). New York: IEEE, p. 9, 2012.
dc.identifier.doi10.1109/INDUSCON.2012.6451400
dc.identifier.lattes6427185658143370
dc.identifier.scopus2-s2.0-84874404368
dc.identifier.urihttp://hdl.handle.net/11449/73822
dc.identifier.wosWOS:000318021500021
dc.language.isoeng
dc.relation.ispartof2012 10th IEEE/IAS International Conference on Industry Applications, INDUSCON 2012
dc.rights.accessRightsAcesso aberto
dc.sourceScopus
dc.subjectClass A
dc.subjectCommercial electronics
dc.subjectCurrent generation
dc.subjectElectronic energy meter
dc.subjectEnergy measure
dc.subjectEnergy meters
dc.subjectHarmonic components
dc.subjectIEEE 1459-2010
dc.subjectInput datas
dc.subjectInstantaneous power theory
dc.subjectInternal algorithms
dc.subjectMathlab
dc.subjectNon-sinusoidal
dc.subjectPower analyzers
dc.subjectPractical experimentation
dc.subjectThree-phase four-wire
dc.subjectUnbalanced circuit
dc.subjectWave forms
dc.subjectExperiments
dc.subjectIndustrial applications
dc.subjectElectric measuring instruments
dc.titlePractical comparisons among electronic energy meters, a precision energy meter and IEEE1459 for reactive energy measurements, under unbalanced and non-sinusoidal conditionsen
dc.typeTrabalho apresentado em evento
dcterms.licensehttp://www.ieee.org/publications_standards/publications/rights/rights_policies.html
dspace.entity.typePublication
unesp.author.lattes6427185658143370
unesp.campusUniversidade Estadual Paulista (UNESP), Faculdade de Engenharia, Ilha Solteirapt
unesp.departmentEngenharia Elétrica - FEISpt

Arquivos