dc.description.abstractThis paper proposes a new methodology to control the power flow between a distributed generator (DG) and the electrical power distribution grid. It is used the droop voltage control to manage the active and reactive power. Through this control a sinusoidal voltage reference is generated to be tracked by voltage loop and this loop generates the current reference for the current loop. The proposed control introduces feed-forward states improving the control performance in order to obtain high quality for the current injected to the grid. The controllers were obtained through the linear matrix inequalities (LMI) using the D-stability analysis to allocate the closed-loop controller poles. Therefore, the results show quick transient response with low oscillations. Thus, this paper presents the proposed control technique, the main simulation results and a prototype with 1000VA was developed in the laboratory in order to demonstrate the feasibility of the proposed control. © 2012 IEEE.en
dc.description.affiliationPower Electronics Laboratory - Electrical Engineering Department São Paulo State University - UNESP - FE/IS, Av. José Carlos Rossi, 1370, Ilha Solteira 15385-000
dc.description.affiliationUnespPower Electronics Laboratory - Electrical Engineering Department São Paulo State University - UNESP - FE/IS, Av. José Carlos Rossi, 1370, Ilha Solteira 15385-000
dc.identifierhttp://dx.doi.org/10.1109/INDUSCON.2012.6451392
dc.identifier.citation2012 10th IEEE/IAS International Conference on Industry Applications, INDUSCON 2012.
dc.identifier.doi10.1109/INDUSCON.2012.6451392
dc.identifier.lattes6427185658143370
dc.identifier.scopus2-s2.0-84874436546
dc.identifier.urihttp://hdl.handle.net/11449/73820
dc.identifier.wosWOS:000318021500013
dc.language.isoeng
dc.relation.ispartof2012 10th IEEE/IAS International Conference on Industry Applications, INDUSCON 2012
dc.rights.accessRightsAcesso aberto
dc.sourceScopus
dc.subjectActive and Reactive Power
dc.subjectClosed loop controllers
dc.subjectControl performance
dc.subjectControl techniques
dc.subjectCurrent loop
dc.subjectCurrent reference
dc.subjectD stability
dc.subjectDistributed generators
dc.subjectDroop control
dc.subjectElectrical power
dc.subjectFeed-Forward
dc.subjectHigh quality
dc.subjectLCL filters
dc.subjectPower flow controls
dc.subjectPower flows
dc.subjectSingle-phase inverters
dc.subjectSinusoidal voltage
dc.subjectVoltage loops
dc.subjectControllers
dc.subjectDistributed power generation
dc.subjectIndustrial applications
dc.subjectLinear matrix inequalities
dc.subjectRobust control
dc.subjectQuality control
dc.titleRobust control applied to power flow control in single-phase inverter with LCL filter, using droop control and D-stabilityen
dc.typeTrabalho apresentado em evento
dcterms.licensehttp://www.ieee.org/publications_standards/publications/rights/rights_policies.html
dspace.entity.typePublication
unesp.author.lattes6427185658143370[5]
unesp.author.orcid0000-0003-3853-5994[5]
unesp.campusUniversidade Estadual Paulista (UNESP), Faculdade de Engenharia, Ilha Solteirapt
unesp.departmentEngenharia Elétrica - FEISpt

Arquivos