Publicação: Assessment of Macro Fiber Composite Sensors for Measurement of Acoustic Partial Discharge Signals in Power Transformers
dc.contributor.author | De Castro, Bruno Albuquerque [UNESP] | |
dc.contributor.author | De Melo Brunini, Danilo [UNESP] | |
dc.contributor.author | Baptista, Fabricio Guimaraes [UNESP] | |
dc.contributor.author | Andreoli, Andre Luiz [UNESP] | |
dc.contributor.author | Ulson, Jose Alfredo Covolan [UNESP] | |
dc.contributor.institution | Universidade Estadual Paulista (Unesp) | |
dc.date.accessioned | 2018-12-11T17:33:58Z | |
dc.date.available | 2018-12-11T17:33:58Z | |
dc.date.issued | 2017-09-15 | |
dc.description.abstract | This paper presents a performance assessment of macro fiber composite (MFC) sensors for measuring acoustic emission (AE) signals from partial discharges (PD) in power transformers filled with mineral oil. MFC sensors are low-profile and flexible, allowing them to be attached to uneven surfaces, such as a transformer wall. Two types of MFC sensors were assessed: P1 (d33 effect) and P2 (d31 effect), which are optimized for different deformations in the structure, such as elongation and contraction, respectively. In addition, a conventional AE sensor, R15I-AST model from Physical Acoustics South America, was also used as a reference for comparative analysis. Four metrics were applied to the signals: root mean square, energy criterion, Akaike criterion, power spectral density, and correlation. The experimental results indicate a high similarity between the MFC sensors and the conventional AE sensor, which expands the research field in acoustic PD measurement in power transformers by using low-cost and flexible sensors. | en |
dc.description.affiliation | São Paulo State University (UNESP) School of Engineering Department of Electrical Engineering | |
dc.description.affiliationUnesp | São Paulo State University (UNESP) School of Engineering Department of Electrical Engineering | |
dc.format.extent | 6090-6099 | |
dc.identifier | http://dx.doi.org/10.1109/JSEN.2017.2735858 | |
dc.identifier.citation | IEEE Sensors Journal, v. 17, n. 18, p. 6090-6099, 2017. | |
dc.identifier.doi | 10.1109/JSEN.2017.2735858 | |
dc.identifier.file | 2-s2.0-85028909027.pdf | |
dc.identifier.issn | 1530-437X | |
dc.identifier.scopus | 2-s2.0-85028909027 | |
dc.identifier.uri | http://hdl.handle.net/11449/179152 | |
dc.language.iso | eng | |
dc.relation.ispartof | IEEE Sensors Journal | |
dc.rights.accessRights | Acesso aberto | |
dc.source | Scopus | |
dc.subject | acoustic emission | |
dc.subject | low cost system | |
dc.subject | MFC Sensor | |
dc.subject | partial discharges | |
dc.subject | transformers | |
dc.title | Assessment of Macro Fiber Composite Sensors for Measurement of Acoustic Partial Discharge Signals in Power Transformers | en |
dc.type | Artigo | |
dspace.entity.type | Publication | |
unesp.author.lattes | 8962036732560069[4] | |
unesp.author.orcid | 0000-0003-4581-1459[1] | |
unesp.author.orcid | 0000-0002-1200-4354[3] | |
unesp.author.orcid | 0000-0002-7271-397X[4] | |
unesp.department | Engenharia Elétrica - FEB | pt |
Arquivos
Pacote Original
1 - 1 de 1
Carregando...
- Nome:
- 2-s2.0-85028909027.pdf
- Tamanho:
- 2.02 MB
- Formato:
- Adobe Portable Document Format
- Descrição: