This paper evaluates the influence of frequency-dependent soil conductivity and permittiv-ity in the transient responses of single-and double-circuit transmission lines including the ground wires subjected to lightning strikes. We use Nakagawa’s approach to compute the ground-return impedance and admittance matrices where the frequency-dependent soil is modeled using Alípio and Visacro’s model. We compare some elements of these matrices with those calculated by Carson’s approach which assumes the frequency constant. Results show that a significant difference can be obtained in high resistive soils for these elements in impedance and admittance matrices. Then, we compute the transient responses for single-and double-circuit lines with ground wires located above soils of 500, 1000, 5000, and 10,000 Ω·m considering the frequency constant and frequency-dependent parameters generated for two lightning strikes (subsequent stroke and Gaussian pulse). We demonstrate that the inclusion of frequency dependence of soil results in an expressive reduction of approximately 26.15% and 42.75% in the generated voltage peaks in single-and double-circuit lines located above a high-resistive soil. These results show the impact of the frequency-dependent soils that must be considered for a precise transient analysis in power systems.

Descrição

Palavras-chave

Electromagnetic transient analysis, Ground-return admittance, Ground-return impedance, Lightning, Transmission lines

Idioma

Inglês

Como citar

Energies, v. 14, n. 17, 2021.

Itens relacionados

Unidades

Departamentos

Cursos de graduação

Programas de pós-graduação