Resumo

This paper explains why the reliability assessment of energy limited systems requires more detailed models for primary generating resources availability, internal and external generating dispatch and customer demand than the ones commonly used for large power systems and presents a methodology based on the full sequential Montecarlo simulation technique with AC power flow for their long term reliability assessment which can properly include these detailed models. By means of a real example, it is shown how the simplified modeling traditionally used for large power systems leads to pessimistic predictions if it is applied to an energy limited system and also that it cannot predict all the load point adequacy problems. © 2006 IEEE.

Descrição

Palavras-chave

Interconnected power system, power system reliability, power system simulation, AC power flow, Customer demands, Detailed models, Large power systems, Load points, Monte Carlo Simulation, Power system simulations, Real example, Reliability assessments, Computer simulation, Electric power system interconnection, Power transmission, Rating, Reliability analysis, Electric power transmission

Idioma

Inglês

Como citar

2006 IEEE PES Transmission and Distribution Conference and Exposition: Latin America, TDC'06.