Alternative parameterization for assessing branch outages by a continuation method
dc.contributor.author | Matarucco, R. R. | |
dc.contributor.author | Alves, D. A. [UNESP] | |
dc.contributor.author | Da Silva, L. C.P. | |
dc.contributor.author | Castro, C. A. | |
dc.contributor.institution | University Center of Votuporanga (UNIFEV) | |
dc.contributor.institution | Universidade Estadual Paulista (UNESP) | |
dc.contributor.institution | Universidade Estadual de Campinas (UNICAMP) | |
dc.date.accessioned | 2022-04-28T20:01:14Z | |
dc.date.available | 2022-04-28T20:01:14Z | |
dc.date.issued | 2004-12-01 | |
dc.description.abstract | This paper proposes and tests new parameters, namely the voltage magnitudes, phase angles and the total power losses, for evaluating the effects of branch outages. The approach can be used as a verification tool after a list of critical contingencies had been ranked according to their severities by the contingency selection function. It is then possible to find whether the non-convergence of a power flow is due to a numerical problem or to an infeasible operating situation. Besides, the proposed parameters have a clear physical meaning rather than geometrical and allow the development and application of continuation methods for power systems contingency analysis. The main advantage of using the total real power losses as a parameter is that it is not necessary to change parameters during the solutions tracing until beyond the simple limit point, where the original Jacobian is singular. Results are presented for the IEEE 14 and 57 bus test system. © 2004 IEEE. | en |
dc.description.affiliation | University Center of Votuporanga (UNIFEV), CEP 15500-000, Votuporanga, SP | |
dc.description.affiliation | Department of Electrical Engineering School of Electrical Engineering State University of São Paulo (UNESP), Cx. P. 31, CEP 15385-000, Ilha Solteira, SP | |
dc.description.affiliation | School of Electrical and Computer Engineering State University of Campinas (UNICAMP), Cx. P. 6101, CEP 13081-970, Campinas, SP | |
dc.description.affiliationUnesp | Department of Electrical Engineering School of Electrical Engineering State University of São Paulo (UNESP), Cx. P. 31, CEP 15385-000, Ilha Solteira, SP | |
dc.format.extent | 39-44 | |
dc.identifier.citation | 2004 IEEE/PES Transmission and Distribution Conference and Exposition: Latin America, p. 39-44. | |
dc.identifier.scopus | 2-s2.0-22744447870 | |
dc.identifier.uri | http://hdl.handle.net/11449/224575 | |
dc.language.iso | eng | |
dc.relation.ispartof | 2004 IEEE/PES Transmission and Distribution Conference and Exposition: Latin America | |
dc.source | Scopus | |
dc.subject | Contingency analysis | |
dc.subject | Continuation Method | |
dc.subject | Parameterization | |
dc.subject | Voltage Stability | |
dc.title | Alternative parameterization for assessing branch outages by a continuation method | en |
dc.type | Trabalho apresentado em evento | |
unesp.department | Engenharia Elétrica - FEIS | pt |