Transient Responses on Transmission Lines Located above Frequency-Dependent Soil with Variable Water Content
Carregando...
Arquivos
Fonte externa
Fonte externa
Data
Orientador
Coorientador
Pós-graduação
Curso de graduação
Título da Revista
ISSN da Revista
Título de Volume
Editor
Tipo
Trabalho apresentado em evento
Direito de acesso
Arquivos
Fonte externa
Fonte externa
Resumo
This paper investigates the influence of frequency-dependent soil parameters with variable water content in the transient responses of single-circuit three-phase transmission line (TL) subjected to lightning subsequent return stroke. For this purpose, we use the Nakagawa's approach to compute the ground-return impedance and admittance matrices the frequency-dependent soil modeled by Messier is employed. With the Nakagawa's approach, four water contents of 0.90%, 2.57%, 4.04% and 11.57% are selected with results in low-frequency resistivity of 5000, 1000, 500 and 100 Ω.m. The transient responses for single-circuit three-phase line located above soils of 100, 500, 1000, and 5000 Ω.m considering the frequency-constant soil using the Carson's approach are compare. Results demonstrated that the inclusion of frequency dependence of soil leads to an expressive reduction of approximately 19.52% and 60.16% in the generated voltage peaks (first and third) for this TL located above a high-resistive soil of 5000 Ω.m and lower water content W = 0.90%. This work shows the impact of the frequency-dependent soil that must be taken into account for adequate transient in power systems.
Descrição
Palavras-chave
frequency-dependent soils, lightning, transient analysis, transmission lines, water content
Idioma
Inglês
Citação
2021 Workshop on Communication Networks and Power Systems, WCNPS 2021.