Improved Fault Location on Distribution Feeders Based on Matching During-Fault Voltage Sags
Nenhuma Miniatura disponível
Data
2009-04-01
Orientador
Coorientador
Pós-graduação
Curso de graduação
Título da Revista
ISSN da Revista
Título de Volume
Editor
Institute of Electrical and Electronics Engineers (IEEE)
Tipo
Artigo
Direito de acesso
Acesso restrito
Resumo
A fault location algorithm for distribution feeders based on matching during-fault voltage sags is presented. The basic principle of the algorithm is based on the fact that when a fault occurs on the feeder, voltage sags propagate presenting different characteristics for each feeder node. Knowing the voltage sag characteristics, it is possible to locate the faulty node or the faulty area of the feeder. This voltage-based approach ensures the efficiency and robustness of the algorithm, which provides suitable and accurate results. An overhead, three-phase, three-wire, 13.8 kV, 134-node, real-life feeder model is used to evaluate the algorithm. Test results show that the algorithm is quite suitable due to not only the faulted point being located, but also a faulted area being identified providing important information to direct the maintenance crew seeking to repair any fault inflicted damage.
Descrição
Palavras-chave
Idioma
Inglês
Como citar
IEEE Transactions on Power Delivery. Piscataway: IEEE-Inst Electrical Electronics Engineers Inc, v. 24, n. 2, p. 852-862, 2009.