A New Method for Fault Location in Distribution Networks Based on Voltage Sag Measurements

dc.contributor.authorFonseca Buzo, Ricardo
dc.contributor.authorBarradas, Henrique Molina
dc.contributor.authorLeao, Fabio Bertequini
dc.contributor.institutionUniversidade Estadual Paulista (Unesp)
dc.date.accessioned2020-12-12T02:24:36Z
dc.date.available2020-12-12T02:24:36Z
dc.date.issued2020-01-01
dc.description.abstractThis paper presents an innovative method for fault location in distribution networks based on classical circuit analyses. Two synchronized and few nonsynchronized pre- and during-fault voltages are required at few buses along with the impedance matrix. A new impedance matrix manipulation procedure is proposed so that the distribution system is investigated in partitions across multiple subsystems. This procedure allows the fault location process to be performed by solving systems of determined equations, making the method more technically accessible. The fault is located by analyzing the voltage sag at the terminal-bus of each subsystem separately. The proposed method is validated on the IEEE 33-bus, 12.66 kV distribution system with/without distributed generation (DG). Simulation results show the robustness and accuracy of the method under several pre- and during-fault scenarios and measurements errors.en
dc.description.affiliationElectrical Engineering, Sao Paulo State University-UNESP, Ilha Solteira, Sao Paulo Brazil (e-mail: ricardobuzo00@hotmail.com)
dc.description.affiliationElectrical engineering, Sao Paulo State University - UNESP, Ilha Solteira, So Paulo Brazil (e-mail: henrique1226@hotmail.com)
dc.description.affiliationElectrical Engineering, Sao Paulo State University-UNESP, Ilha Solteira, Sao Paulo Brazil 15385-000 (e-mail: bertequini@dee.feis.unesp.br)
dc.identifierhttp://dx.doi.org/10.1109/TPWRD.2020.2987892
dc.identifier.citationIEEE Transactions on Power Delivery.
dc.identifier.doi10.1109/TPWRD.2020.2987892
dc.identifier.issn1937-4208
dc.identifier.issn0885-8977
dc.identifier.scopus2-s2.0-85083711502
dc.identifier.urihttp://hdl.handle.net/11449/201120
dc.language.isoeng
dc.relation.ispartofIEEE Transactions on Power Delivery
dc.sourceScopus
dc.subjectClassical technique
dc.subjectCurrent measurement
dc.subjectdistributed generation
dc.subjectdistribution networks
dc.subjectFault currents
dc.subjectFault location
dc.subjectfault location
dc.subjectImpedance
dc.subjectPhasor measurement units
dc.subjectPower quality
dc.subjectVoltage measurement
dc.subjectvoltage measurements
dc.titleA New Method for Fault Location in Distribution Networks Based on Voltage Sag Measurementsen
dc.typeArtigo
unesp.departmentEngenharia Elétrica - FEISpt

Arquivos