Publicação:
Study of the electrical Power quality in the common connection point between a 7.8 kWp PV system and a low-voltage network

dc.contributor.authorValverde-Granja, Agustin
dc.contributor.authorSouza, Teofilo M. de [UNESP]
dc.contributor.authorMagalhaes-Sobrinho, Pedro [UNESP]
dc.contributor.institutionUniv Ibague
dc.contributor.institutionUniversidade Estadual Paulista (Unesp)
dc.date.accessioned2018-11-26T16:04:28Z
dc.date.available2018-11-26T16:04:28Z
dc.date.issued2018-01-01
dc.description.abstractAn experimental 1,000 kWh/month PV solar system was connected to a low-voltage network at the Universidad de Ibague, Colombia. In this work, we present the findings about the electrical voltage issues in the common connection point. The characterization of the low-voltage network was based on the NTC 5001standard, including aspects such as voltage imbalance, intermittency, short and long-term flicker, and harmonics. The maximum energy production was 850 kWh /month, equal to the 72.65% of the total installed capacity. In this condition, the minimum voltage measurements evidenced a 2 % increase from the previous value, the voltage imbalance was 3.5 to 70 percent lower, and the voltage harmonics (TDH) increased 7, 0.8 and 3 percent in the phases U-1, U-2 and U-3, respectively. Current harmonics did not show significant increases in lines U-2 and U-3, line U-1 recorded an increase of 22%, but there were no significant variations in the short and long-term flicker, notches and interruptions. Regarding the electrical power, the active and reactive components increased 58 and 42%, respectively, and the thermographic study indicated a 7.5 percent increasing temperature after the installation of the experimental PV system. This experience aims to be a reference project in the implementation of the Act 1715 of the Colombian government to promote solaren
dc.description.affiliationUniv Ibague, Fac Engn, Ibague, Colombia
dc.description.affiliationUniv Estadual Paulista UNESP, Fac Engn, Sao Paulo, Brazil
dc.description.affiliationUnespUniv Estadual Paulista UNESP, Fac Engn, Sao Paulo, Brazil
dc.format.extent63-73
dc.identifierhttp://dx.doi.org/10.25100/iyc.v20i1.4222
dc.identifier.citationIngenieria Y Competitividad. Cali: Univ Valle, Fac Ingenieria, v. 20, n. 1, p. 63-73, 2018.
dc.identifier.doi10.25100/iyc.v20i1.4222
dc.identifier.issn0123-3033
dc.identifier.urihttp://hdl.handle.net/11449/160436
dc.identifier.wosWOS:000438794200006
dc.language.isoeng
dc.publisherUniv Valle, Fac Ingenieria
dc.relation.ispartofIngenieria Y Competitividad
dc.rights.accessRightsAcesso restrito
dc.sourceWeb of Science
dc.subjectLow voltage network
dc.subjectPower quality
dc.subjectsolar PV system
dc.subjectexperimental network
dc.titleStudy of the electrical Power quality in the common connection point between a 7.8 kWp PV system and a low-voltage networken
dc.typeArtigo
dcterms.rightsHolderUniv Valle, Fac Ingenieria
dspace.entity.typePublication

Arquivos

Coleções